Parker Air Preparation Products | FRLs | Proportional Regulator Programming Information
How to Change Parameters
Pressing the Accept key ("acc") for more than 3 seconds will active parameter change mode. The user can then select the parameters by pressing the up or down key. When parameter number is correct, pressing Accept again will enter parameter number. Display will show parameter value.
Pressing the up or down key will change the parameter itself. Display will flash indicating parameter editing mode. Pressing the Accept key will accept the new parameter value. All digits will flash while being accepted.
After releasing all keys, the next parameter number will be presented on the display. When no key is pressed after 3 seconds, the display will show the actual output pressure. When unit is initially powered up allow approximately 10 seconds for the unit to boot-up before changing parameter settings. Parameter numbers 0, 4, 6, 8, 9, 12, 13, 14, 18, 19, 20, and 21 are accessible to edit. All other parameters are fixed.
Back to Proportional Regulators Main Page
Parameter 0 - Reset Back to Factory Settings
After start up, entering this value in parameter 0 will store the calibrated factory data into the working parameters.
Step | 1 | 2 | 3 | 4 | 5 | |
Press: |
3-6 seconds |
![]() |
|
![]() |
|
|
Until Display Reads: | Pxx | P00 |
000. (Flashing Decimal) |
003. (Flashing Decimal) |
003 (Flashing) |
P01 |
Description | Accesses changable parameters. | Accesses parameter no 0. | Displays current parameter value. | Edits parameter. 3= standard factory settings. If other than 3, use Up or Down Arrow and accept 3. | Accepts and saves new parameter setting. | Sequences to next parameter. |
Parameter 4 - Set Control Signal in Volts or Milliamps
The unit is factory set for 0-10V control signal. If 4-20mA control signal is required, change parameter 4.
Step | 1 | 2 | 3 | 4 | 5 | |
Press: |
3-6 seconds |
![]() |
|
![]() |
|
|
Unit Display Reads: | Pxx | P04 |
001. (Flashing Decimal) |
000. (Flashing Decimal) |
000 (Flashing) |
P05 |
Description | Accesses changeable parameters. | Accesses parameter no. 4. |
Displays current parameter value. 1= V 0=mA |
Edits parameter. | Accepts and saves new parameter setting. | Sequences to next parameter. |
Parameter 6 - Set Output Signal
Parameter 6 is used to set the type of output signal to your PLC. This parameter is used as follows:
Output Signal Option 0= Digital Output - PNP
- Factory set at "0", Non-Adjustable
Output Signal Option P= Digital PNP or Analog 1-10V
- Factory set at "1" for Analog Signal
- Concert to Digital PNP by changing parameter to "0" setting
Output Signal Option N= Digital NPN or Analog 1-10V
- Factory set at "1" Analog Signal
- Convert to Digital NPN by changing parameter to "0" setting
Output Signal Option M= Analog 4-20 mA
- Factory set at "2", Non-Adjustable
Step | 1 | 2 | 3 | 4 | 5 | |
Press: |
3-6 seconds |
![]() |
|
![]() |
|
|
Unit Display Reads: | Pxx | P06 |
001. (Flashing Decimal) |
# # #. (Flashing Decimal) (Value 0, 1 or 2) |
# # #. (Flashing) |
P07 |
Description: | Accesses changeable parameters. | Accesses parameter no. 6. |
Displays current parameter value. 1= m factory default for P3H with analog options |
Edits parameter. 0= digital (NPN or PNP) 1= analog 0..10V 2= analog 4..20 mA |
Accepts and saves new parameter setting. | Sequences to next parameter. |
Parameter 8 - Adjust Span Analog Output Signal
Set value is a % of Full Analog range. As an example, for a 0-10V output signal, the original factory setting of 100% will give you an adjustment of 0-10V. If you reset Parameter 8 to 50%, the new output range would be 0-5V, or 50% of the full range.
Step | 1 | 2 | 3 | 4 | 5 | |
Press: |
3-6 seconds |
![]() |
|
![]() |
|
|
Until Display Reads: | Pxx | P08 |
100. (Flashing Decimal) For 2 bar versions value=92 |
# # #. (Flashing Decimal) (Value between 0 and 130) |
# # #. (Flashing) |
P09 |
Description: | Accesses changeable parameters. | Accesses parameter no. 8. | Displays current parameter value. | Edits parameter. | Accepts and saves new parameter setting and implements the new analog signal span. | Sequences to next parmeter. |
Parameter 9 - Adjust Digital Display Value (Pressure Calibration)
If necessary, adjustments can be made to the digital display when using an external pressure sensor.
Step | 1 | 2 | 3 | 4 | 5 | |
Press: |
3-6 seconds |
![]() |
|
![]() |
|
|
Until Display Reads: | Pxx | P09 |
# # #. (Flashing Decimal) |
# # #. (Flashing Decimal) |
# # # (Flashing) |
P10 |
Description: | Accesses changeable parameters. | Accesses parameter no. 9. | Displays current digital display. | Use up or down arrows to adjust the display value if using an external pressure sensor. | Accepts and saves new parameter setting. | Sequences to next parmeter. |
Parameter 12 - Set Proportional Band (P20 Must be Set to 0)
Proportional band is used for setting the reaction sensitivity of the regulator. The displayed value is X 10 mbar and has a range between 50 (0.5 bar) and 250 (2.5 bar).
Step | 1 | 2 | 3 | 4 | 5 | |
Press: |
3-6 seconds |
![]() |
|
![]() |
|
|
Until Display Reads: | Pxx | P12 |
100. (Flashing Decimal) |
# # #. (Flashing Decimal) (Value between 50 and 250) |
# # # (Flashing) |
P13 |
Description: | Accesses changeable parameters. | Accesses parameter no. 12. |
Displays current parameter value. Incremental value is: X 10 mbar |
Edits parameter. | Accepts and saves new parameter setting. | Sequences to next parmeter. |
Parameter 13 - Set Deadband (P20 Must be Set to 0)
Deadband is the minimum limit of accuracy at which the regulator is set for normal operation. The displayed value is X 10 mbar and has a range of between 4 (40 mbar) and 40 (400 mbar).
Step | 1 | 2 | 3 | 4 | 5 | |
Press: |
3-6 seconds |
![]() |
|
![]() |
|
|
Until Display Reads: | Pxx | P13 |
015. (Flashing Decimal) |
# # #. (Flashing Decimal) (Value between 4 and 40) |
# # # (Flashing) |
P14 |
Description: | Accesses changeable parameters. | Accesses parameter no. 13. |
Displays current parameter value.
Incremental value is: X 10 mbar |
Edits parameter. | Accepts and saves new parameter setting. | Sequences to next parmeter. |
Parameter 14 - Set Pressure Scale in psig or bar
Units with NPT port threads are supplied with a factory set psig pressure scale. Use parameter 14 to change scale to bar.
Step | 1 | 2 | 3 | 4 | 5 | |
Press: |
3-6 seconds |
![]() |
|
![]() |
|
|
Until Display Reads: | Pxx | P14 |
001. (Flashing Decimal) |
000. (Flashing Decimal) |
000 (Flashing) |
P15 |
Description: | Accesses changeable parameters. | Accesses parameter no. 14. |
Displays current parameter value. 1=psig 0=bar 2=-MPA |
Edits parameter. | Accepts and saves new parameter setting. | Sequences to next parmeter. |
Parameter 18 - Set Minimum Preset Pressure
If there is a need for a preset minimum pressure, use parameter 18. (Note: preset pressure is affected by %P19.)
Step | 1 | 2 | 3 | 4 | 5 | |
Press: |
3-6 seconds |
![]() |
|
![]() |
|
|
Until Display Reads: | Pxx | P18 |
000. (Flashing Decimal) |
# # #. (Flashing Decimal) (Value between 0 and 200) |
# # # (Flashing) |
P15 |
Description: | Accesses changeable parameters. | Accesses parameter no. 18. |
Displays current parameter value. Incremental value is: 2 bar unit: x 2 mbar x %P19 10 bar unit: x 10 mbar x %P19 |
Edits parameter. | Accepts and saves new parameter setting. | Sequences to next parmeter. |
Parameter 19 - Set Maximum Preset Pressure
Pressure correction allows the user to set a maximum pressure as a percentage of secondary pressure F.S.
Example: If F.S. is 10 bar, set parameter 19 to 50 for maximum preset pressure of 5 bar.
Pressure correction also affects the minimum preset pressure in parameter 18.
Example: If F.S. is 10 bar and parameter 18 is set to a value of 100 (1 bar), and parameter 19 is set to 50%, then the actual minimum pressure seen is 0.5 bar.
Step | 1 | 2 | 3 | 4 | 5 | |
Press: |
3-6 seconds |
![]() |
|
![]() |
|
|
Until Display Reads: | Pxx | P19 |
100. (Flashing Decimal) |
# # #. (Flashing Decimal) (Value between 0 and 100) |
# # # (Flashing) |
P20 |
Description | Accesses changable parameters. | Accesses parameter no 19. |
Displays current parameter value. Incremental value is: % of F.S. |
Edits parameter. | Accepts and saves new parameter setting. | Sequences to next parameter. |
Parameter 20 - Set Behavior Control
The regulation speed of the pressure regulator can be modified with Parameter 20. The value in this parameter has a range from 0-5. A higher value indicates slower regulation speed, but will be more stable.
Step | 1 | 2 | 3 | 4 | 5 | |
Press: |
3-6 seconds |
![]() |
|
![]() |
|
|
Until Display Reads: | Pxx | P20 |
003. (Flashing Decimal) |
# # #. (Flashing Decimal) (Value between 0 and 5) |
# # # (Flashing) |
P21 |
Description | Accesses changable parameters. | Accesses parameter no 20. |
Displays current parameter value. |
Edits parameter. 0= custom set 1= fastest (narrow proportional band) 2= fast 3= normal 4= slow 5= slowest (broad proportional band) |
Accepts and saves new parameter setting. | Sequences to next parameter. |
Parameter 21 - Set Proportional Effect (P20 Must be Set to 0)
Step | 1 | 2 | 3 | 4 | 5 | |
Press: |
3-6 seconds |
![]() |
|
![]() |
|
|
Until Display Reads: | Pxx | P21 |
010. (Flashing Decimal) |
# # #. (Flashing Decimal) (Value between 5 and 100) |
# # # (Flashing) |
P22 |
Description | Accesses changable parameters. | Accesses parameter no 21. |
Displays current parameter value. |
Edits parameter. 5= fastest regulation |
Accepts and saves new parameter setting. | Sequences to next parameter. |
Parameter 39 - Displays Current Software Version
Step | 1 | 2 | 3 |
Press: |
3-6 seconds |
![]() |
|
Until Display Reads: | Pxx | P39 |
# # #. (Flashing Decimal) |
Description | Accesses changable parameters. | Accesses parameter no 21. |
Displays current parameter value. XXX= Current software version. |

Proportional Regulators
Parker Air Preparation
Global Air Prep- Modular design allows for quick component change - no need to disconnect piping
- Can be used without modular connectors using existing piping
- Wide selection of sizes and options
- Proven design, widely used
- Suitable for most corrosive environments
- Flows to 150 SFFM
- Pressures to 500 PSIG
Electronic Proportional Regulators
- All controls on the same face
- Highly visible LED Display
- Modular Mounting